4.18.5 Password function (Pr. 296, Pr. 297)

Registering a 4-digit password can restrict parameter reading/writing.
Parameter
Name
Number
296
Password lock level
*1*4
297
Password lock/unlock
*2*4
*1
This parameter can be set when Pr. 160 User group read selection = "0".
*2
If Pr. 296 = "9999" (no password lock), Pr. 297 can be set while Pr. 160 = "0." When the password lock is valid, Pr. 297 can be set regardless of the
Pr. 160 setting.
*3
"0 or 9999" can be set to Pr.297 at any time although the setting is invalid (the displayed value does not change).
*4
This parameter allows its setting to be changed during operation in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write
selection.
(1) Parameter reading/writing restriction level (Pr. 296 )
Level of reading/writing restriction by PU/Network(NET) mode operation command can be selected by Pr. 296.
PU Mode Operation Command
Pr. 296 Setting
Read
9999
0, 100
×
*6
1, 101
2, 102
3, 103
×
4, 104
×
5, 105
6, 106
Only the parameters registered in the user group can be read/written.
99, 199
(For the parameters not registered in the user group, same restriction level as "4, 104" applies.)
*1
If the parameter reading is restricted by the Pr. 160 setting, those parameters are unavailable for reading even when " " is indicated.
*2
If the parameter writing is restricted by the Pr. 77 setting, those parameters are unavailable for writing even when " " is indicated.
*3
Parameter access from unit where parameter is written in PU operation mode (initially set to operation panel (FR-DU07), parameter unit) is
restricted. (Refer to page 219 for PU mode operation command source selection)
*4
This restricts parameter access from the command source that can write a parameter under Network operation mode (initially RS-485 terminal or
a communication option). (Refer to page 219 for NET mode command source.)
*5
Read/write is enabled only in the simple mode parameters registered in the user group when Pr.160 User group read selection = "9999". Pr.296 and
Pr.297 are always read/write enabled whether registered to a user group or not.
*6
If a communication option is installed, option fault (E.OPT) occurs, and inverter trips. (Refer to page 318.)
Initial Value
9999
9999
*3
Write
*1
*2
×
×
×
×
×
Misoperation prevention and parameter
Setting Range
0 to 6, 99, 100 to
Select restriction level of parameter reading/
106, 199
writing when a password is registered.
9999
No password lock
1000 to 9998
Register a 4-digit password
Displays
(0 to 5)
(Reading only)
*3
(Valid when Pr. 296 = "100" to "106")
9999
Password being unlocked
*3
PU Mode Operation Command
Read
Communication
RS-485 terminal
×
×
×
*5
setting restriction
Description
password
unlock
error
*4
Write
*2
Read
option
×
×
×
×
×
: enabled, ×: restricted
count.
4
203