Selection of operation mode and
operation location

4.19 Selection of operation mode and operation location

Purpose
Operation mode selection
Started in network operation mode
Selection of operation location

4.19.1 Operation mode selection (Pr. 79)

Used to select the operation mode of the inverter.
Mode can be changed as desired between operation using external command signals (external operation), operation
from the PU (FR-DU07/FR-PU04/FR-PU07), combined operation of PU operation and external operation (external/PU
combined operation, and network operation (when RS-485 terminals or a communication option is used).
Parameter Number
79
Operation mode selection
The above parameters can be changed during a stop in any operation mode.
POINT
• Use the easy setting mode to set Pr. 79 in simple steps. (Refer to page 62)
Pr.79
Setting
Use External/PU switchover mode
0
Press
to switch between the PU and External operation mode.
At power ON, the inverter is in the External operation mode.
Operation mode
1
PU operation mode (fixed)
External operation mode (fixed)
The operation can be performed
2
by switching between the
External and NET operation
modes.
External/PU combined
3
operation mode 1
External/PU combined
4
operation mode 2
Switchover mode
6
Switch among PU operation, External operating, and NET operation while keeping the
same operating status.
External operation mode (PU operation interlock)
X12 signal ON: Operation mode can be switched to the PU operation mode.
7
(output stop during External operation)
X12 signal OFF: Operation mode cannot be switched to the PU operation mode.
*1
This parameter allows its setting to be changed in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write selection.
*2
The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog
input (AU) > digital input from the operation panel".
REMARKS
If switching of the operation mode is invalid even though Pr. 79 is set, refer to 5.5.9 Operation mode is not changed properly (page 327).
206
Parameter that must be set
Operation mode selection
Operation mode at power ON
Selection of start command source, speed
command source and operation location
during communication operation
Name
Description
Frequency command
Setting by the operation
panel (FR-DU07) and PU
(FR-PU04/FR-PU07)
External signal input (from
terminal 2, 4, and 1, JOG,
multi-speed selection, etc.)
PU (FR-DU07/FR-PU04/FR-
PU07) setting or external
signal input (multi-speed
setting, across terminals 4
and 5 (valid when AU signal
turns ON)).
*2
External signal input
(Terminal 2, 4, 1, JOG, multi-
speed selection, etc.)
Pr. 79
Pr. 79, Pr. 340
Pr. 338, Pr. 339,
Pr. 550, Pr. 551
Initial Value
Setting Range
0
0 to 4, 6, 7
Start command
Input by
and
on
PU (FR-DU07/FR-PU04/FR-
PU07)
External signal input (from
terminal STF and STR)
External signal input (from
terminal STF and STR)
Input by
and
on
PU (FR-DU07/FR-PU04/FR-
PU07)
Refer to page
206
218
219
Refer
LED Indication
to
: OFF
: ON
page
PU operation mode
External operation mode
209
NET operation mode
PU operation mode
209
External operation mode
209
NET operation mode
210
External/PU combined
operation mode
210
PU operation mode
211
External operation mode
211
NET operation mode