Operation Setting At Fault Occurrence; Retry Function (Pr. 65, Pr. 67 To Pr. 69) - Mitsubishi Electric FR-F720P-0.75K to 110K Instruction Manual

Fr-f700p series
Hide thumbs Also See for FR-F720P-0.75K to 110K:
Table of Contents

Advertisement

Operation setting at fault occurrence

4.14 Operation setting at fault occurrence

Purpose
Recover by retry operation at fault
occurrence
Output fault code from terminal
Do not input/output phase loss alarm

4.14.1 Retry function (Pr. 65, Pr. 67 to Pr. 69)

If a fault occurs, the inverter resets itself automatically to restart. You can also select the fault for a retry.
When automatic restart after instantaneous power failure is selected (Pr. 57 Restart coasting time ≠ "9999"), restart
operation is performed at retry operation as at an instantaneous power failure. (Refer to page 162 for the restart
function.)
Parameter
Number
65
Retry selection
Number of retries at fault
67
occurrence
68
Retry waiting time
69
Retry count display erase
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201)
Retry success example
Pr.68
Pr.68
Inverter
output
frequency
0
Retry start
Fault occurrence
Retry success count
ON
Y64
Retry failure example
Pr.68
Inverter
output
frequency
0
First
retry Fault
Fault
occurrence
occurrence
Fault signal
(ALM)
ON
Y64
172
Retry operation
Fault code output function
Input/output phase loss
protection selection
Initial
Name
Value
0
0
1s
0
Retry success
5
Time
Success count + 1
Pr.68
Pr.68
Second
Third
retry Fault
retry
Retry failure
occurrence
ON
ON
ON
Parameter that must be Set
Pr. 65, Pr. 67 to Pr. 69
Setting
Range
0 to 5
A fault for retry can be selected. (Refer to the next page)
0
No retry function
Set the number of retries at fault occurrence.
1 to 10
A fault output is not provided during retry operation.
Set the number of retries at fault occurrence. (The
101 to 110
setting value of minus 100 is the number of retries.)
A fault output is provided during retry operation.
Set the waiting time from when an inverter fault occurs
0 to 10s
until a retry is made.
0
Clear the number of restarts succeeded by retry.
⋅ Retry operation automatically resets a fault and
restarts the inverter at the starting frequency when the
time set in Pr. 68 elapses after the inverter is tripped.
⋅ Retry operation is performed by setting Pr. 67 to any
value other than "0". Set the number of retries at fault
occurrence in Pr. 67.
⋅ When retries fail consecutively more than the number
of times set in Pr. 67, a retry count excess fault (E.RET)
occurs, resulting in inverter trip.
(Refer to retry failure example)
⋅ Use Pr. 68 to set the waiting time from when the
inverter trips until a retry is made in the range 0 to 10s.
⋅ Reading the Pr. 69 value provides the cumulative
number of successful restart times made by retry. The
cumulative count in Pr. 69 is increased by 1 when a
retry is regarded as successful after normal operation
continues without faults occurring for more than four
times longer than the time set in Pr. 68 after a retry
start.
(When retry is successful, cumulative number of retry
failure is cleared.)
⋅ Writing "0" in Pr. 69 clears the cumulative count.
Time
⋅ During a retry, the Y64 signal is ON. For the Y64
signal, assign the function by setting "64 (positive
operation)" or "164 (negative operation)" in any of Pr.
(E.RET)
190 to Pr. 196 (output terminal function selection) .
CAUTION
Changing the terminal assignment using Pr. 190 to Pr. 196
(output terminal function selection) may affect the other
functions. Set parameters after confirming the function of
each terminal.
Pr. 76
Pr. 251, Pr. 872
Description
Refer to
Page
172
174
175

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents