Frequency setting by external terminals
4.7.2

Jog operation (Pr. 15, Pr. 16)

You can set the frequency and acceleration/deceleration time for jog operation. Jog operation can be performed
from either the outside or PU.
Can be used for conveyor positioning, test operation, etc.
Parameter
Name
Number
Jog frequency
15
Jog
acceleration/
16
deceleration
time
The above parameters are displayed as simple mode parameters only when the parameter unit (FR-PU04/FR-PU07) is connected. When the
operation panel (FR-DU07) is connected, the above parameters can be set only when Pr. 160 User group read selection = "0". (Refer to page 201)
*1
Performing IPM parameter initialization changes the settings. (Refer to page 80)
*2
When the setting of Pr. 21 Acceleration/deceleration time increments is "0" (initial value), the setting range is "0 to 3600s" and the setting increments
are "0.1s", and when the setting is "1", the setting range is "0 to 360s" and the setting increments are "0.01s"
(1) Jog operation from outside
⋅ When the JOG signal is ON, a start and stop are available by the start signal (STF, STR). (The JOG signal is
assigned to the terminal JOG in the initial setting)
Output
frequency(Hz)
Pr.20
Pr.15
Forward
Jog frequency
rotation
setting range
Pr.16
JOG signal
Forward
rotation STF
ON
Reverse
rotation STR
1.
Screen at power-ON
Confirm that the External operation mode is selected.
([EXT] lit)
If not lit, press
External [EXT] operation mode.
If the operation mode still does not change,
set Pr. 79 to change to the External operation mode.
2.
Turn the JOG switch ON.
3.
Turn the start switch (STF or STR) ON.
The motor rotates while start switch
(STF or STR) is ON.
Rotates at 5Hz. (Initial value of Pr. 15)
4.
Turn the start switch (STF or STR) OFF.
REMARKS
⋅ When you want to change the running frequency, change Pr. 15 Jog frequency . (initial value "5Hz")
⋅ When you want to change the acceleration/deceleration time, change Pr. 16 Jog acceleration/deceleration time . (initial value
"0.5"s)
104
Initial
Setting Range
Value
0 to 400Hz
5Hz
*1
0.5s
0 to 3600/360s
*2
Time
Reverse
rotation
ON
ON
Operation
to change to the
Set the frequency for jog operation.
Set the acceleration/deceleration time for jog operation. As the
acceleration/deceleration time set the time taken to reach the
frequency set in Pr. 20 Acceleration/deceleration reference
frequency. (Initial value is 60Hz
The acceleration and deceleration times cannot be set
separately.
Three-phase AC
power supply
Forward rotation start
Reverse rotation start
JOG signal
Connection diagram for external jog operation
ON
Forward
rotation
ON
Reverse
rotation
Forward
rotation
Reverse
rotation
OFF
Description
)
*1
Inverter
R/L
U
1
S/L
V
2
T/L
W
3
STF
STR
JOG
SD
10
2
5
Indication
Rotates while ON
Stop
Motor