Function assignment of external
terminal and control
Setting
Signal
Positive
Negative
Name
Logic
Logic
96
196
REM
98
198
LF
99
199
ALM
9999
*1
Note that when the frequency setting is varied using an analog signal or
frequency) signal may alternate ON and OFF depending on that varying speed and the timing of the varying speed due to acceleration/
deceleration time setting. (The output will not alternate ON and OFF when the acceleration/deceleration time setting is "0s".)
*2
When a power supply reset is performed, the fault output 2 signal (ALM2) turns OFF as soon as the power supply switches OFF.
REMARKS
⋅ The same function may be set to more than one terminal.
⋅ When the function is executed, the terminal conducts at the setting of any of "0" to "99", and does not conduct at the setting of
any of "100" to "199".
⋅ When Pr. 76 Fault code output selection = "1", the output signals of the terminals SU, IPF, OL and FU are switched as set in Pr. 76.
(When an inverter fault occurs, the signal output is switched to the fault code output.)
⋅ The output assignment of the terminal RUN and fault output relay are as set above regardless of Pr. 76.
CAUTION
⋅ Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection) may affect the other functions. Set
parameters after confirming the function of each terminal.
⋅ Do not assign signals which repeat frequent ON/OFF to terminal ABC1, terminal ABC2. Otherwise, the life of the relay contact
decreases.
(2) Inverter operation ready signal (RY signal) and inverter running signal (RUN, RUN3 signal)
Power
ON
supply
ON
STF
RH
Pr. 13
Starting
frequency
Reset
processing
ON
RY
RUN
ON
RUN3
Inverter
Start
Start
Status
Signal is
Signal is
OFF
ON
(during
(during
Output
stop)
stop)
Signal
RY
ON
RUN
OFF
OFF
RUN3
OFF
*1
This signal turns OFF during power failure or undervoltage.
*2
Output is shutoff in conditions like a fault and when the MRS signal is ON.
REMARKS
⋅ RUN signal is assigned to the terminal RUN in the initial setting.
⋅ During IPM motor control, the RUN signal is output about 100ms after turning ON the start command (STF, STR). The delay is
due to the magnetic pole detection.
142
Function
Output to the terminal when a value is set to
Remote output
the parameter.
Output when an alarm (fan failure or
Alarm output
communication error warning) occurs.
Output when the fault occurs. The signal
Fault output
output is stopped when the fault is reset.
No function
OFF
OFF
ON
DC injection brake
operation point
DC injection
brake
operation
Time
OFF
ON
OFF
OFF
Start
Signal is
Under DC
ON
Injection
(during
Brake
running)
ON
ON
ON
ON
OFF
ON
ON
ON
Operation
of the operation panel (FR-DU07), the output of the SU (up to
⋅ When the inverter is ready to operate, the output of the
operation ready signal (RY) is ON. It is also on during inverter
running.
⋅ When the inverter's output frequency reaches Pr. 13 Starting
frequency or higher (0.01Hz under IPM motor control), the
inverter running signal (RUN) is output. During an inverter
stop or DC injection brake operation, the output is OFF.
⋅ The output of the RUN3 signal is ON when the inverter
running and start signals are ON.
(For the RUN3 signal, output is ON if the starting command is
ON even when a fault occurs or the MRS signal is ON.
When using the RY, RUN and RUN3 signals, assign functions to
Pr. 190 to Pr. 196 (output terminal selection function) referring to the
table below.
Output
Pr. 190 to Pr. 196 Setting
Signal
Positive logic
RY
11
RUN
0
RUN3
45
Output Shutoff
*2
Start Signal
Start Signal
is ON
is OFF
OFF
OFF
ON
OFF
Related
Parameters
Pr. 495 to Pr. 497
Pr. 121, Pr. 244
Negative logic
111
100
145
Automatic Restart after
Instantaneous Power Failure
Coasting
Restarting
Start Signal
Start Signal
is ON
is OFF
ON
*1
OFF
ON
OFF
Refer
to Page
148
229,
281
143
ON
ON
ON