Cleaning; Replacement Of Parts - Mitsubishi Electric FR-F720P-0.75K to 110K Instruction Manual

Fr-f700p series
Hide thumbs Also See for FR-F720P-0.75K to 110K:
Table of Contents

Advertisement

6.1.6

Cleaning

Always run the inverter in a clean status.
When cleaning the inverter, gently wipe dirty areas with a soft cloth immersed in neutral detergent or ethanol.
CAUTION
Do not use solvent, such as acetone, benzene, toluene and alcohol, as they will cause the inverter surface paint to peel off.
The display, etc. of the operation panel (FR-DU07) and parameter unit (FR-PU04/FR-PU07) are vulnerable to detergent and
alcohol. Therefore, avoid using them for cleaning.
6.1.7

Replacement of parts

The inverter consists of many electronic parts such as semiconductor devices.
The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced
performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically.
Use the life check function as a guidance of parts replacement.
Part Name
Cooling fan
Main circuit smoothing capacitor
On-board smoothing capacitor
Relays
Fuse (185K or higher)
*1
Estimated lifespan for when the yearly average surrounding air temperature is 40°C
(without corrosive gas, flammable gas, oil mist, dust and dirt etc)
*2
Output current : 80% of the inverter rated current
CAUTION
For parts replacement, consult the nearest Mitsubishi FA Center.
Estimated lifespan
*1
10 years
10 years
*2
10 years
10 years
Inspection item
Description
Replace (as required)
Replace (as required)
Replace the board (as required)
as required
Replace the fuse (as required)
6
335

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents