Operation selection at power failure and
instantaneous power failure

4.13.3 Power failure signal (Y67 signal)

When output is shutoff due to a power failure or undervoltage, the Y67 signal turns ON regardless of the automatic
restart after instantaneous power failure function setting.
Y67 signal turns OFF at power failure recovery or undervoltage recovery.
To use Y67 signal, set "67 (positive logic) or 167 (negative logic)" in any of Pr. 190 to Pr. 192 (Output terminal function
selection) to assign the function.
Recovery after power failure
Power supply
ON
Output frequency
Y67
OFF
CAUTION
⋅ Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other functions. Set
parameters after confirming the function of each terminal.
♦ Parameters referred to ♦
Pr. 190 to Pr. 196 (output terminal function selection)
168
OFF
ON
Time
ON
OFF
Refer to page 140
Converter voltage recovery after E.UVT
Power supply
Output frequency
Y67
OFF
ON
ON
E.UVT occurrence
Time
Converter voltage recovery