Operation Selection Function 2 (Pr. 65 To Pr. 79); Retry Function (Pr. 65, Pr. 67 To Pr. 69) - Mitsubishi Electric FR-V500 Instruction Manual

High precision & fast response vector inverter
Hide thumbs Also See for FR-V500:
Table of Contents

Advertisement

(5) Protective functions
If any of the following errors occurs in the brake sequence mode, the inverter results in an alarm, shuts off the
output, and turns off the brake opening request signal (BOF terminal).
On the control panel (FR-DU04
Error Display
(Detected speed) - (output speed) > Pr. 285 during vector control.
E.MB1
(Overspeed detection function)
Deceleration is not normal during deceleration operation (Use Pr. 284 to select this function.)
E.MB2
(Except stall prevention operation)
Brake opening request signal (BOF) turned on though the motor is at a stop.
E.MB3
(Gravity drop prevention function)
More than 2s after the run command (forward or reverse rotation) is input, the brake opening request signal
E.MB4
(BOF) does not turn on.
Although more than 2s have elapsed after the brake opening request signal (BOF) turned on, the brake
E.MB5
opening completion signal (BRI) does not turn on.
Though the inverter had turned on the brake opening request signal (BOF), the brake opening completion
E.MB6
signal (BRI) turned off midway.
Although more than 2s have elapsed after the brake opening request signal (BOF) turned off at a stop, the
E.MB7
brake opening completion signal (BRI) does not turn off.

3.11 Operation selection function 2 (Pr. 65 to Pr. 79)

3.11.1 Retry function (Pr. 65, Pr. 67 to Pr. 69
When the inverter output is stopped by the protective function (major fault), this function causes the inverter to
automatically reset itself to make a retry. You can select whether retry operation is to be performed or not,
alarms reset for retry, number of retries made, and waiting time.
Parameter
Name
65
Retry selection
Number of retries at alarm
67
occurrence
68
Retry waiting time
Retry count display
69
erasure
<Setting>
• Use Pr. 65 to select the protective functions (major faults) to be activated for retries.
Errors Reset for Retry
Error definition
Acceleration overcurrent
Constant-speed overcurrent
Deceleration overcurrent
Acceleration overvoltage
Constant-speed overvoltage
Deceleration overvoltage
Motor thermal relay
Transistor thermal relay
Instantaneous power failure
Undervoltage
Brake transistor
Earth (Ground) fault protection
Output phase failure
External thermal relay
Stall prevention-triggered stop
Option alarm
Option 1 alarm
Operation selection function 2 (Pr. 65 to Pr. 79)
) LED or parameter unit (FR-PU04V) screen, the following errors are displayed:
-1
Factory
Setting Range
Setting
0
0
1s
0
Abbreviation
0
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E.BE
E.GF
E.LF
E.OHT
E.OLT
E.OPT
E.OP1
109
Description
)
speed
torque
Remarks
0 to 5
0, 1 to 10,
101 to 110
Extended mode
0 to 10s
0
Pr. 65
1
2
3
4
5
Remarks
3