(2) Operation example
• At start: When the start signal is input to the inverter, the inverter starts running. When the internal speed
command reaches the value set in Pr. 278 and the output current is not less than the value set in Pr.
279, the inverter outputs the brake opening request signal (BOF) after the time set in Pr. 280 has
elapsed.
When the time set in Pr. 281 has elapsed after the brake opening completion signal (BRI) was input, the
inverter increases the internal speed command to the set speed.
• At stop: When the speed has decreased to the speed set in Pr. 282, the brake opening request signal (BOF) is
turned off. When the time set in Pr. 283 has elapsed after the brake operation confirmation signal (BRI)
was input, the inverter output is switched off.
*If Pr. 60 = "8" (mechanical brake opening completion signal not input), this time is the time after the
brake opening request signal is output.
1. Pr. 60 = "7" (brake opening completion signal input)
Input speed command value
Brake opening request
Brake opening completion
Electromagnetic brake operation
2. Pr. 60 = "8" (mechanical brake opening completion signal not input)
Input speed command value
Brake opening request
Electromagnetic brake
Target speed
Pr.278
Pr.280
Pr.13
STF
Output I
(BOF signal)
(BRI signal)
Closed
Target speed
Pr.278
Pr.280
Pr.13
STF
Output I
(BOF signal)
Closed
operation
Brake sequence (Pr. 60, Pr. 278 to Pr. 285)
Pr.282
Pr.281
ON
Pr.279
ON
ON
Opened
Pr.282
Pr.281
ON
Pr.279
ON
Opened
107
Pr.278
Pr.283
Closed
Time
Pr.278
Pr.283
Closed
Time
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-v520Fr-v540

Table of Contents