Mitsubishi Electric FR-V500 Instruction Manual page 114

High precision & fast response vector inverter
Hide thumbs Also See for FR-V500:
Table of Contents

Advertisement

CAUTION
• The range of speed changeable by RH
(acceleration) and RM (deceleration) is 0 to
maximum speed (Pr. 1 setting). Note that the
maximum value of set speed is (main speed +
maximum speed).
• When the acceleration or deceleration signal turns on, the set speed varies according to the slope set
in Pr. 44 "second acceleration/deceleration time" or Pr. 45 "second deceleration time". The output
speed acceleration/deceleration times are as set in Pr. 7 "acceleration time" and Pr. 8 "deceleration
time", respectively. Therefore, the longer preset times are used to vary the actual output speed. (Refer
to page 27 for the set speed and output speed.)
• If the start signal (STF or STR) is off, turning on the RH (acceleration) or RM (deceleration) signal varies
the set speed.
When selecting this function, re-set Pr. 1 "maximum speed" according to the machine.
Related parameters
• RH, RM, RL signal terminal assignment ⇒ Pr. 180 to Pr. 183, Pr. 187 (input terminal function selection) (Refer to page 150.)
• Maximum speed setting ⇒ Pr. 1 "maximum speed" (Refer to page 76.)
• Output speed acceleration/deceleration time ⇒ Pr. 7 "acceleration time", Pr. 8 "deceleration time" (Refer to page 78.)
• Time setting for acceleration/deceleration ⇒ Pr. 44 "second acceleration/deceleration time", Pr. 45 "second deceleration time"
(Refer to page 78.)
• RH, RM, RL signal compensation ⇒ Pr. 28 "multi-speed input compensation" (Refer to page 88.)
(Hz)
Output frequency is
clamped at Pr. 1
Pr. 1
Main speed setting
0Hz
Acceleration(RH)
Deceleration(RM)
Forward rotation(STF)
CAUTION
105
Additional functions (Pr. 59)
The set speed is clamped at (main speed + Pr. 1 )
Set speed
Output speed
ON
ON
ON
Time
3