Offline auto tuning (Pr. 80 to Pr. 96)
(3)
Monitoring during execution
When the parameter unit (FR-PU04V) is used, the Pr. 96 value is displayed during tuning on the main monitor as
shown below. When the control panel (FR-DU04-
When Pr. 96 = 1
• Parameter unit (FR-PU04V) main monitor
1. Setting
Display
• Control panel (FR-DU04-
1. Setting
Displayed
value
REMARKS
• Offline auto tuning time (factory setting)
1: No-rotation mode: Approx. 25s
2: Rotation mode: Approx. 40s
(Offline auto tuning time varies with the acceleration and deceleration time settings as indicated below.
Offline auto tuning time = acceleration time + deceleration time + approx. 30s)
(4) Ending the offline auto tuning
1)
Confirm the Pr. 96 value.
• Normal end:
"3" or "103" is displayed.
• Error end:
"9", "91", "92" or "93" is displayed.
• Forced end:
"8" is displayed.
2)
When tuning ended normally
For PU operation, press
This operation resets the offline auto tuning and the PU's monitor display returns to the normal indication.
(Without this operation, next operation cannot be started.)
Do not change the Pr. 96 setting after completion of tuning.
If the Pr. 96 setting is changed, tuning data is made invalid.
If the Pr. 96 setting is changed, tuning must be performed again.
3)
When tuning was ended due to an error
Offline auto tuning did not end normally. (The motor constants have not been set.) Reset the inverter and start
tuning all over again.
4)
Error display definitions
Error
Display
9
Inverter trip
91
Current limit (stall prevention) function was activated.
92
Converter output voltage reached 75% of rated value. Check for fluctuation of power supply voltage.
93
Calculation error
No connection with motor will also result in "93" error.
) is used, the same value as on the PU is only displayed.
1
2. Tuning in progress
TUNE
1
STOP
PU
STF
FWD
) display
1
2. Tuning in progress
STOP
. For external operation, turn off the start signal (STF or STR) once.
RESET
Error Cause
3. Completion
TUNE
3
2
COMPLETION
STF
STOP
PU
PU
3. Completion
Make setting again.
Increase acceleration/deceleration time. Set "1" in Pr. 156.
Check the motor wiring and make setting again.
122
4. Error-activated end
(for inverter trip)
TUNE
9
ERROR
STF
STOP
PU
4. Error-activated end
(for inverter trip)
Remedy