4.8 All parameter clear

POINT
· Set "1" in ALLC parameter clear to initialize all parameters. (Parameters are not cleared when "1" is set in Pr. 77
Parameter write selection. In addition, calibration parameters are not cleared.)
· Refer to the extended parameter list on page 102 for parameters to be cleared with this function.
1.
Screen at powering on
The monitor display appears.
2.
Press
to choose the PU operation
mode.
3.
Press
to choose the parameter
setting mode.
4.
Turn
until
clear) appears.
5.
Press
to read the currently set
value.
"
"(initial value) appears.
6.
Turn
clockwise to change it to
the setting value of " ".
7.
Press
to set.
and
The inverter is not in the PU operation mode.
1. Press
2. Carry out operation from step 6 again.
Operation
(all parameter
· Press
to read another parameter.
· Press
to show the setting again.
· Press
twice to show the next parameter.
are displayed alternately ... Why?
.
is lit and the monitor (4 digit LED) displays "0" (Pr.79 = "0" (initial value)).
Display
PU indication is lit.
The parameter
number read
previously appears.
Flicker ··· Parameter setting complete!!
All parameter clear
59