Extended parametersExtended parameters
Parameter
Name
Communication
EEPROM write
342
selection
Communication
343
error count
Protocol selection
549
Terminal 2
125
frequency setting
gain frequency
Terminal 4
126
frequency setting
gain frequency
Analog input display
241
unit switchover
Terminal 2
C2
frequency setting
(902)
bias frequency
Terminal 2
C3
frequency setting
(902)
bias
Terminal 2
C4
frequency setting
(903)
gain
Terminal 4
C5
frequency setting
(904)
bias frequency
Terminal 4
C6
frequency setting
(904)
bias
Terminal 4
C7
frequency setting
(905)
gain
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04).
112
Incre
Initial
Range
ments
Value
Parameter values written by
0
communication are written to the EEPROM
and RAM.
1
0
Parameter values written by
1
communication are written to the RAM.
Display the number of communication
errors during Modbus-RTU communication.
1
0
(read only)
Read only.
Displayed only when Modbus-RTU protocol
is selected.
Mitsubishi inverter
0
(computer link)
protocol
1
1
Modbus-RTU
1
protocol
Set the frequency of terminal 2 input gain
0.01Hz
60Hz
0 to 400Hz
(maximum).
Set the frequency of terminal 4 input gain
0.01Hz
60Hz
0 to 400Hz
(maximum).
0
Displayed in %
1
0
1
Displayed in V/mA
Set the frequency on the bias side of
0.01Hz
0Hz
0 to 400Hz
terminal 2 input.
Set the converted % of the bias side
0.1%
0%
0 to 300%
voltage (current) of terminal 2 input.
Set the converted % of the gain side
0.1%
100%
0 to 300%
voltage of terminal 2 input.
Set the frequency on the bias side of
0.01Hz
0Hz
0 to 400Hz
terminal 4 input.
Set the converted % of the bias side
0.1%
20%
0 to 300%
current (voltage) of terminal 4 input.
Set the converted % of the gain side
0.1%
100%
0 to 300%
current (voltage) of terminal 4 input.
Param
eter
copy
Description
× : disabled
×
After setting
change, reset
(switch power off,
then on) the
inverter.
The setting change
is reflected after a
reset.
Select the unit for
analog input display.
All
Param
param
eter
eter
clear
clear
: enabled
×
×
×
×
×
×
×
×
×
×