2 INSTALLATION AND WIRING

Three-phase AC power supply
Use within the permissible power supply
specifications of the inverter.
(Refer to page 90)
Moulded case circuit
breaker (MCCB)
or earth leakage circuit
breaker (ELB), fuse
The breaker must be selected carefully since
an in-rush current flows in the inverter at
power on.
(Refer to page 3)
Magnetic contactor(MC)
Install the magnetic contactor to ensure safety.
Do not use this magnetic contactor to start and
stop the inverter.
Doing so will cause the inverter life to be shorten.
(Refer to page 3)
Reactor (FR-HAL, FR-HEL)
Reactors (option) should be used when power
harmonics measures are taken, the power factor
is to be improved or the inverter is installed near a
large power supply system (1000kVA or more).
The inverter may be damaged if you do not use
reactors.
Select the reactor according to the model.
Remove the jumpers across terminals P/+-P1 to
connect to the DC reactor.
(Refer to the Instruction Manual (applied).)
AC reactor
(FR-HAL)
Noise filter
(FR-BLF)
It is not necessary
for the 200V class and
the FR-F740-01160 or less.
High power factor
converter
(FR-HC, MT-HC
)
*2
Power supply harmonics
can be greatly suppressed.
Install this as required.
*1 Compatible with the 200V class and the FR-F740-01160 or less.
*2 Compatible with the FR-F740-01800 or more.
CAUTION
· Do not install a power factor correction capacitor or surge suppressor on the inverter output side. This will cause the inverter
to trip or the capacitor, and surge suppressor to be damaged. If any of the above devices are connected, immediately
remove them.
· Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication
devices (such as AM radios) used near the inverter. In this case, set the EMC filter valid to minimize interference.
(Refer to the Instruction Manual (applied).)
· Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.
2
PLC
DC reactor
(FR-HEL)
For the FR-F740-01800
or more, a DC reactor is
supplied.
Power regeneration
common converter
Resistor unit
(FR-CV
)
*1
(FR-BR
Power regeneration
converter (MT-RC
)
The regenerative braking
*2
Greater braking capability
capability of the inverter can be
is obtained.
exhibited fully.
Install this as required.
Install this as required.
Inverter
(FR-F700)
The life of the inverter is influenced by ambient
temperature. The ambient temperature should be as low
as possible within the permissible range. Especially when
mounting the inverter inside an enclosure, take cautions
of the ambient temperature. (Refer to page 6)
RS-485 terminal block
Wrong wiring might lead to damage of the inverter. The
The inverter can be
control signal lines must be kept fully away from the main
circuit to protect them from noise.(Refer to page 8)
connected with computers
Refer to page 23 for the built-in EMC filter.
such as PLC.
It supports Mitsubishi inverter
protocol and Modbus-RTU
(binary) protocol.
R/L1 S/L2 T/L3
P/+
P1
P/+
N/-
Ground
Brake unit
(FR-BU
, MT-BU5
)
*1
*2
Devices connected to the output
P/+
PR
Do not install a power factor correction capacitor,
P/+
surge suppressor or radio noise filter on the output
PR
side of the inverter.
When installing a moulded case circuit breaker on the
output side of the inverter, contact each manufacturer
for selection of the moulded case circuit breaker.
, MT-BR5
)
*1
*2
Ground
To prevent an electric shock, always ground the
motor and inverter.
Noise filter
(FR-BSF01, FR-BLF)
Install a noise filter to reduce
the electromagnetic noise
U V W
generated from the inverter.
Effective in the range from
about 1MHz to 10MHz.
When more wires are passed
through, a more effective result
can be obtained.
Motor
Ground