Appendix 2 Extended Parameters - Mitsubishi Electric FR-F700 Series Instruction Manual

Fr-f700 series
Hide thumbs Also See for FR-F700 Series:
Table of Contents

Advertisement

Extended parametersExtended parameters

Appendix 2 Extended parameters

indicates simple mode parameters.
Parameter
Name
0
Torque boost
Second torque
46
boost
Maximum
1
frequency
2
Minimum frequency
High speed
maximum
18
frequency
3
Base frequency
Base frequency
19
voltage
Second V/F (base
47
frequency)
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
24
Multi-speed setting
to
4 speed to 7 speed
27
232
Multi-speed setting
to
8 speed to 15
speed
239
102
Incre
Initial
Range
ments
Value
Set the output voltage at 0Hz as %.
*1
6/4/3/2/
0.1%
0 to 30%
1.5/1%
*1
Set the torque boost when the RT signal
0 to 30%
is on.
0.1%
9999
9999
Without second torque boost
Set the upper limit of the output frequency.
120/
*2
0.01Hz
0 to 120Hz
60Hz
*2
0.01Hz
0Hz
0 to 120Hz Set the lower limit of the output frequency.
Set when performing the operation at
120Hz or more.
120/
0.01Hz
120 to 400Hz
*3
60Hz
*3
Set the frequency when the motor rated
0.01Hz
60Hz
0 to 400Hz
torque is generated. (50Hz/60Hz)
0 to 1000V
Set the base voltage.
0.1V
9999
8888
95% of power supply voltage
9999
Same as power supply voltage
Set the base frequency when the RT
0 to 400Hz
signal is on.
0.01Hz
9999
9999
Second V/F is invalid
0.01Hz
60Hz
0 to 400Hz Set frequency when the RT signal is on.
0.01Hz
30Hz
0 to 400Hz
Set frequency when the RM signal is on.
0.01Hz
10Hz
0 to 400Hz
Set frequency when the RL signal is on.
0 to 400Hz,
0.01Hz
9999
Frequency from 4 speed to 15 speed can
9999
be set according to the combination of the
RH, RM, RL and REX signals.
0 to 400Hz,
9999: not selected
0.01Hz
9999
9999
Description
Initial values differ according to the
inverter capacity.
Inverter capacity
200V class
400V class
00046
00023
00077 to 00167
00038 to 00083
00250, 00340
00126, 00170
00490 to 01540
00250 to 00770
01870 or more
00930, 01160
-
01800 or more
The setting depends on the inverter
capacity (200V class and FR-F740-
01160 or less/FR-F740-01800 or more)
The setting depends on the inverter
capacity (200V class and FR-F740-
01160 or less/FR-F740-01800 or more)
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled
Initial
value
6%
4%
3%
2%
1.5%
1%

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents