Control Circuit Terminals - Mitsubishi Electric FR-F700 Series Instruction Manual

Fr-f700 series
Hide thumbs Also See for FR-F700 Series:
Table of Contents

Advertisement

Wiring
2.4.4

Control circuit terminals

indicates that terminal functions can be selected from Pr. 178 to Pr. 196 (I/O terminal function selection) (
Instruction Manual (applied).)
(1) Input signals
Terminal
Terminal
Symbol
Name
Forward
STF
rotation start
Reverse
STR
rotation start
Start self-
STOP
holding
selection
RH,
Multi-speed
RM, RL
selection
Jog mode
JOG
selection
Second
acceleration/
RT
deceleration
time
selection
MRS
Output stop
RES
Reset
Terminal 4
input selection
AU
PTC input
Selection of
automatic
CS
restart after
instantaneous
power failure
Contact input
SD
common
(sink)
External
transistor
common,
24VDC
PC
power supply,
contact input
common
(source)
16
Description
Turn on the STF signal to start forward
rotation and turn it off to stop.
Turn on the STR signal to start reverse
rotation and turn it off to stop.
Turn on the STOP signal to self-hold the start signal.
Multi-speed can be selected according to the combination of
RH, RM and RL signals.
Turn on the JOG signal to select Jog operation (initial setting)
and turn on the start signal to start Jog operation.
Turn on the RT signal to select second acceleration/
deceleration time.
When the second function such as "second torque boost" and
"second V/F (base frequency)" are set, turning on the RT
signal selects these functions.
Turn on the MRS signal (20ms or more) to stop the inverter
output.
Use to shut off the inverter output when stopping the motor by
electromagnetic brake.
Used to reset alarm output provided when protective function
is activated.
Turn on the RES signal for more than 0.1s, then turn it off.
Initial setting is for reset always. By setting Pr.75, reset can be
set to enabled only at an inverter alarm occurrence. Recover
about 1s after reset is cancelled.
Terminal 4 is made valid only when the AU signal is turned on. (The
frequency setting signal can be set between 4 and 20mADC.)
Turning the AU signal on makes terminal 2 (voltage input) invalid.
AU terminal is used as PTC input terminal (thermal protection
of the motor). When using it as PTC input terminal, set the AU/
PTC switch to PTC.
When the CS signal is left on, the inverter restarts automatically at
power restoration. Note that restart setting is necessary for this
operation. In the initial setting, a restart is disabled.
(Refer to Pr.57 Restart coasting time, in Instruction Manual (applied).)
Common terminal for contact input terminal and terminal CA
for sink logic.
Common output terminal for 24VDC 0.1A power supply (PC
terminal).
Isolated from terminals 5 and SE.
When connecting the transistor output (open collector output),
such as a programmable controller (PLC), connect the external
power supply common for transistor output to this terminal to
prevent a malfunction caused by undesirable currents.
Can be used as 24VDC 0.1A power supply.
When source logic has been selected, this terminal serves as
NO contact input common.
Specifications
When the STF and
STR signals are turned
on simultaneously, the
stop command is given.
Input resistance
4.7kΩ
Voltage at
opening: 21 to
27VDC
Contacts at
short-circuited: 4
to 6mADC
Power supply
voltage range
19.2 to 28.8VDC
Current
consumption
100mA
Refer to the
Rated
Refer to
42
Instruction
Manual
(applied).
44
Instruction
Manual
(applied).
Instruction
Manual
(applied).
Instruction
Manual
(applied).
74
48
Instruction
Manual
(applied).
Instruction
Manual
(applied).
-- -- - -- -- -- - -- -- - -- -
22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents