Mitsubishi Electric FR-F700 Series Instruction Manual page 114

Fr-f700 series
Hide thumbs Also See for FR-F700 Series:
Table of Contents

Advertisement

Parameter
Name
Analog input
73
selection
Terminal 1 added
compensation
242
amount (terminal 2)
Terminal 1 added
compensation
243
amount (terminal 4)
Override bias
252
Override gain
253
Terminal 4 input
267
selection
4mA input check
573
selection
Input filter time
74
constant
Reset selection/
disconnected PU
75
detection/PU stop
selection
Alarm code output
76
selection
Parameter write
77
selection
Reverse rotation
78
prevention selection
Extended parametersExtended parameters
Incre
Initial
Range
ments
Value
Input specification (0 to 5V, 0 to 10V) of
0 to 7,
terminal 2 and 1 can be selected.
1
1
10 to 17
Override and reversible operation can be
selected.
Set the ratio of added compensation
0.1%
100%
0 to 100%
amount when terminal 2 is the main
speed.
Set the ratio of added compensation
0.1%
75%
0 to 100%
amount when terminal 4 is the main
speed.
Set the bias side compensation value of
0.1%
50%
0 to 200%
override function.
Set the gain side compensation value of
0.1%
150%
0 to 200%
override function.
0
Terminal 4 input 4 to 20mA
1
0
1
Terminal 4 input 0 to 5V
2
Terminal 4 input 0 to 10V
When the current input drops to or below
2mA, the LF signal is output and inverter
1
continues operation at the frequency just
1
9999
before current reaches 2mA.
9999
4mA input is not checked.
The primary delay filter time constant for
1
1
0 to 8
the analog input can be set.
A larger setting results in a larger filter.
You can select the reset input
acceptance, disconnected PU (FR-
DUO7) connector detection function
and PU stop function, and reset
restriction (400V class 01800 or more).
0 to 3,
14 to 17
For the initial value, reset always
1
14
100 to 103,
enabled, without disconnected PU
114 to 117*
detection, with PU stop function, and
without reset restriction (FR-F740-
01800 or more) are set.
* 100 to 103 and 114 to 117 can be set only
0
Without alarm code output
1
With alarm code output
1
0
Alarm code output at alarm occurrence
2
only
0
Write is enabled only during a stop
1
Parameter write is disabled.
1
0
Parameter write is enabled in any
2
operation mode regardless of operation
status.
Both forward and reverse rotations
0
allowed
1
Reverse rotation disallowed
1
0
2
Forward rotation disallowed
Description
for FR-F740-01800 or more.
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled
×
×
×
×
109