Appendix 4 Instructions for UL and cUL

(Conforming standard UL 508C, CSA C22.2 No.14)
(1) Installation
This inverter is UL-listed as a product for use in an enclosure.
Design an enclosure so that the inverter ambient temperature, humidity and atmosphere satisfy the specifications.
(Refer to page 92.)
Wiring protection
For installation in the United States, branch circuit protection must be provided in accordance with the National
Electrical Code and any applicable provincial codes.
For installation in Canada, branch circuit protection must be provided in accordance with the Canada Electrical
Code and any applicable provincial codes.
Use the Class RK5 or Class T fuses certified by UL and cUL.
FR-F720-
-NA
Rated voltage(V)
Without power
factor improving
Rated
reactor
current
With power
(A)
factor improving
reactor
FR-F740-
-NA
Rated voltage(V)
Without power
factor improving
Rated
reactor
current
With power
(A)
factor improving
reactor
FR-F740-
-NA
Rated voltage(V)
Without power
factor improving
Rated
reactor
current
With power
(A)
factor improving
reactor
(2) Wiring of the power supply and motor
For wiring the input (R/L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL-listed copper wires
(rated at 75°C(167°F)) and round crimping terminals. Crimp the crimping terminals with the crimping tool
recommended by the terminal maker.
(3) Short circuit ratings
• 200V class
Suitable For Use in A Circuit Capable Of Delivering Not More Than 65kA rms Symmetrical Amperes, 264V
Maximum.
• 400V class
01160 or less
Suitable For Use in A Circuit Capable Of Delivering Not More Than 65kA rms Symmetrical Amperes, 528V
Maximum.
01800 or more
Suitable For Use in A Circuit Capable Of Delivering Not More Than 65kA rms Symmetrical Amperes, 550V
Maximum.
(4) Motor overload protection
When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr.9
Electronic thermal O/L relay.
When connecting multiple motors to the inverter, install an external thermal relay individually.
00046 00077 00105 00167 00250 00340 00490 00630 00770 00930 01250 01540 01870 02330
15
20
30
40
60
15
20
20
30
50
00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160
6
10
15
20
30
6
10
10
15
25
01800 02160 02600 03250 03610
500V or more
300
350
400
500
600
240V or more
80
150
175
200
225
70
125
150
200
200
480V or more
40
70
80
90
110
35
60
70
90
100
300
350
400
500
250
300
350
400
150
175
200
250
125
150
175
200
127