Parameter
Name
PID control
automatic
127
switchover
freqeuncy
128
PID action selection
PID proportional
129
band
130
PID integral time
131
PID upper limit
132
PID lower limit
133
PID action set point
Extended parametersExtended parameters
Incre
Initial
Range
ments
Value
Set the frequency at which the control is
0 to 400Hz
automatically changed to PID control.
0.01Hz
9999
Without PID automatic switchover
9999
function
10
PID reverse action
11
PID forward action
20
PID reverse action
21
PID forward action
50
PID reverse action
1
10
51
PID forward action
60
PID reverse action
61
PID forward action
If the proportional band is narrow
(parameter setting is small), the
manipulated variable varies greatly with a
slight change of the measured value.
0.1 to 1000%
Hence, as the proportional band narrows,
0.1%
100%
the response sensitivity (gain) improves
but the stability deteriorates, e.g. hunting
occurs.
Gain K = 1/proportional band
9999
No proportional control
Time required for only the integral (I)
action to provide the same manipulated
variable as that for the proportional (P)
0.1 to 3600s
action. As the integral time decreases, the
0.1s
1s
set point is reached earlier but hunting
occurs more easily.
9999
No integral control.
Set the upper limit value.
If the feedback value exceeds the setting, the
0 to 100%
FUP signal is output. The maximum input
0.1%
9999
(20mA/5V/10V) of the measured value
(terminal 4) is equivalent to 100%.
9999
No function
Set the lower limit value.
If the measured value falls below the setting
range, the FDN signal is output.
0 to 100%
The maximum input (20mA/5V/10V) of the
0.1%
9999
measured value (terminal 4) is equivalent to
100%.
9999
No function
0 to 100% Used to set the set point for PID control.
0.01%
9999
9999
Terminal 2 input voltage is the set point.
Param
eter
copy
Description
× : disabled
Deviation value
signal (terminal 1)
Measured value
input (terminal 4)
Set value (terminal
2 or Pr. 133)
Deviation value
signal input
(LONWORKS, CC-
Link communication)
Measured value,
set value input
(LONWORKS, CC-
Link communication)
All
Param
param
eter
eter
clear
clear
: enabled
113