Parameter
Name
Life alarm status
255
display
Inrush current limit
256
circuit life display
Control circuit
257
capacitor life
display
Main circuit
258
capacitor life
display
Main circuit
259
capacitor life
measuring
260
Refer to Pr.72.
Power failure stop
261
selection
Subtracted
262
frequency at
deceleration start
Subtraction starting
263
frequency
Power-failure
264
deceleration time 1
Power-failure
265
deceleration time 2
Power failure
deceleration time
266
switchover
frequency
267
Refer to Pr.73.
268
Refer to Pr.52.
269
Parameter for manufacturer setting. Do not set.
331 to 337
Refer to Pr.117 to Pr.124.
Extended parametersExtended parameters
Incre
Initial
Range
ments
Value
Display whether the control circuit
capacitor, main circuit capacitor, cooling
1
0
(0 to 15)
fan, and each parts of the inrush current
limit circuit has reached the life alarm
output level or not.
Display the deterioration degree of the
1%
100%
(0 to 100%)
inrush current limit circuit. Reading only
Display the deterioration degree of the
1%
100%
(0 to 100%)
control circuit capacitor. Reading only
Display the deterioration degree of the
main circuit capacitor. Reading only
1%
100%
(0 to 100%)
The value measured by Pr. 259 is
displayed.
Start measuring the main circuit capacitor life.
Switch the power supply on again and
1
0
0, 1
check the Pr. 259 setting. Measurement is
complete if the setting is "3". Set the
deterioration degree in Pr.258.
Coasting to stop
0
When undervoltage or power failure
occurs, the inverter output is shut off.
When undervoltage or a power failure
1
occurs, the inverter can be decelerated to
1
0
a stop.
When undervoltage or a power failure occurs,
the inverter can be decelerated to a stop.
2
If power is restored during a power failure, the
inverter accelerates again.
Normally operation can be performed with
the initial value unchanged. But adjust the
0.01Hz
3Hz
0 to 20Hz
frequency according to the magnitude of
the load specifications (moment of inertia,
torque).
When output frequency ≥ Pr.263
0 to 120Hz
When output frequency < Pr.263
0.01Hz
60Hz
Decelerate from the speed obtained from
9999
output frequency minus Pr.262.
0.1/
0 to 3600/
Set a deceleration slope down to the
5s
0.01s
360s
frequency set in Pr.266.
0 to 3600/
Set a deceleration slope below the
0.1/
360s
frequency set in Pr.266.
9999
0.01s
9999
Same slope as in Pr.264
Set the frequency at which the
0.01Hz
60Hz
0 to 400Hz
deceleration slope is switched from the
Pr.264 setting to the Pr.265 setting.
Description
Decelerate from the speed obtained
from output frequency minus Pr.262.
Decelerate from output frequency
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled
×
×
×
×
×
×
×
×
×
×
×
×
119