Appendix 5 Instructions for Compliance with the European Directives

(1) EMC Directive
We have self-confirmed our inverters as products compliant to the EMC Directive (second environment of conforming standard
EN61800-3) and place the CE mark on the inverters.
Note:First environment
Environment including residential buildings. Includes buildings directly connected without a transformer to the low voltage power
supply network which supplies power to residential buildings.
Second environment
Environment including all buildings except buildings directly connected without a transformer to the low voltage power supply
network which supplies power to residential buildings.
1) Instructions
Set the EMC filter valid and install the inverter and perform wiring according to the following instructions.
* The inverter is equipped with a built-in EMC filter. Set the EMC filter valid. (The EMC filter is invalid when shipped from the factory.
(The FR-F720-00046 and 00077 are always valid.) For details, refer to page 23.)
* Connect the inverter to an earthed power supply.
* Install a motor and a control cable written in the EMC Installation Manual (BCN-A21041-204) according to the instruction.
* The cable length between the inverter and the motor is 5 m (16.4 feet) maximum.
* Confirm that the inverter complies with the EMC Directive as the industrial drives application for final installation.
(2) Low Voltage Directive
We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard EN 50178) and place
the CE mark on the inverters.
1)Outline of instructions
* Do not use a residual current operated protective device (RCD) as an electric shock protector without connecting the equipment to the
earth. Connect the equipment to the earth securely.
* Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)
* Use the cable sizes on page 13 under the following conditions.
⋅ Ambient temperature: 40°C (104°F) maximum
If conditions are different from above, select appropriate wire according to EN60204 Appendix C TABLE 5.
* Use a tinned (plating should not include zinc) crimping terminal to connect the ground cable. When tightening the screw, be careful not
to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on page 13.
* Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
* Use the residual current operated protective device (RCD) of type B (breaker which can detect both AC and DC). If not, provide double
or reinforced insulation between the inverter and other equipment, or put a transformer between the main power supply and inverter.
* Use the inverter under the conditions of overvoltage category II (usable regardless of the ground condition of the power supply),
overvoltage category III (usable with the earthed-neutral system power supply) and pollution degree 2 or lower specified in IEC664.
⋅ To use the inverter of 00770 or more (IP00) under the conditions of pollution degree 2, install it in the enclosure of IP 2X or higher.
⋅ To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
⋅ To use the inverter of 00620 or less (IP20) outside of an enclosure in the environment of pollution degree 2, fix a fan cover with fan
cover fixing screws enclosed.
FR-F720-00105 to 00250
FR-F740-00083, 00126
* On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
* The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30VDC, 0.3A. (Relay outputs are
basically isolated from the inverter internal circuit.)
* Control circuit terminals on page 8 are safely isolated from the main circuit.
Environment
*
Ambient temperature
Ambient humidity
Maximum altitude
Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). Please contact your sales
representative.
128
Fan cover
fixing screw
Fan cover
Fan
FR-F720-00340 to 00630
FR-F740-00170 to 00380
During Operation
LD: -10°C to +50°C (14°F to 122°F)
SLD (initial setting): -10°C to +40°C
(14°F to 104°F)
90% RH or less
1000m (3280.80feet)
Fan cover
Fan cover
fixing screw
fixing screws
Fan cover
Fan
FR-F720-00770 to 01250
FR-F740-00470, 00620
In Storage
-20°C to +65°C
(-4°F to +149°F)
90% RH or less
1000m (3280.80feet)
Fan cover
Fan
During Transportation
-20°C to +65°C
(-4°F to +149°F)
90% RH or less
10000m (32808feet)