Peripheral Devices - Mitsubishi Electric FR-F700 Series Instruction Manual

Fr-f700 series
Hide thumbs Also See for FR-F700 Series:
Table of Contents

Advertisement

2.1 Peripheral devices

Check the motor capacity of the inverter you purchased. Appropriate peripheral devices must be selected according to the
capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
Motor
Output
Applicable Inverter Type
(kW(HP))
*1
0.75 (1)
FR-F720-00046-NA
1.5 (2)
FR-F720-00077-NA
2.2 (3)
FR-F720-00105-NA
3.7 (5)
FR-F720-00167-NA
5.5 (7.5)
FR-F720-00250-NA
7.5 (10)
FR-F720-00340-NA
11 (15)
FR-F720-00490-NA
15 (20)
FR-F720-00630-NA
18.5 (25)
FR-F720-00770-NA
22 (30)
FR-F720-00930-NA
30 (40)
FR-F720-01250-NA
37 (50)
FR-F720-01540-NA
45 (60)
FR-F720-01870-NA
55 (75)
FR-F720-02330-NA
400V class
Motor
Output
Applicable Inverter Type
(kW(HP))
*1
0.75 (1)
FR-F740-00023-NA
1.5 (2)
FR-F740-00038-NA
2.2 (3)
FR-F740-00052-NA
3.7 (5)
FR-F740-00083-NA
5.5 (7.5)
FR-F740-00126-NA
7.5 (10)
FR-F740-00170-NA
11 (15)
FR-F740-00250-NA
15 (20)
FR-F740-00310-NA
18.5 (25)
FR-F740-00380-NA
22 (30)
FR-F740-00470-NA
30 (40)
FR-F740-00620-NA
37 (50)
FR-F740-00770-NA
45 (60)
FR-F740-00930-NA
55 (75)
FR-F740-01160-NA
75 (100)
FR-F740-01800-NA
90 (125)
FR-F740-01800-NA
110 (150)
FR-F740-02160-NA
132 (200)
FR-F740-02600-NA
160 (250)
FR-F740-03250-NA
185 (300)
FR-F740-03610-NA
*1
Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 200/400VAC 50Hz.
*2
Select the MCCB according to the inverter power supply capacity.
Install one MCCB per inverter.
For installations in the United States or Canada, use the fuse certified by the UL and cUL.
(Refer to page 127.)
*3
The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is used for emergency stop during motor
driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the
MC with class AC-3 rated current for the motor rated current.
*4
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc.
Identify the cause of the trip, then remove the cause and power on the breaker.
Breaker Selection
Reactor connection
without
with
30AF 10A
30AF 10A
30AF 15A
30AF 15A
30AF 20A
30AF 15A
30AF 30A
30AF 30A
50AF 50A
50AF 40A
100AF 60A
50AF 50A
100AF 75A
100AF 75A
225AF 125A
100AF 100A
225AF 150A
225AF 125A
225AF 175A
225AF 150A
225AF 225A
225AF 175A
400AF 250A
225AF 225A
400AF 300A
400AF 300A
400AF 400A
400AF 350A
Breaker Selection
Reactor connection
without
with
30AF 5A
30AF 5A
30AF 10A
30AF 10A
30AF 10A
30AF 10A
30AF 20A
30AF 15A
30AF 30A
30AF 20A
30AF 30A
30AF 30A
50AF 50A
50AF 40A
100AF 60A
50AF 50A
100AF 75A
100AF 60A
100AF 100A
100AF 75A
225AF 125A
225AF 100A
225AF 150A
225AF 125A
225AF 175A
225AF 150A
225AF 200A
225AF 175A
225AF 225A
225AF 225A
225AF 225A
400AF 400A
400AF 400A
400AF 400A
Peripheral devices
Input Side Magnetic
*2
Contactor
Reactor connection
with commercial
power-supply
without
operation
30AF 10A
S-N10
30AF 15A
S-N10
30AF 20A
S-N10
30AF 30A
S-N20, N21 S-N10
50AF 50A
S-N25
100AF 60A
S-N25
100AF 75A
S-N35
225AF 125A
S-N50
225AF 150A
S-N65
225AF 175A
S-N80
225AF 225A
S-N95
400AF 250A
S-N150
400AF 350A
S-N180
600AF 500A
S-N220
Input Side Magnetic
*2
Contactor
with commercial
Reactor connection
power-supply
without
operation
30AF 5A
S-N10
30AF 10A
S-N10
30AF 15A
S-N10
30AF 20A
S-N10
30AF 30A
S-N20
30AF 30A
S-N20
50AF 50A
S-N20
100AF 60A
S-N25
100AF 75A
S-N25
100AF 100A
S-N35
225AF 125A
S-N50
225AF 150A
S-N65
225AF 175A
S-N80
225AF 200A
S-N80
225AF 225A
400AF 300A
400AF 350A
400AF 400A
600AF 500A
600AF 500A
MCCB
MCCB
*3
with
S-N10
S-N10
S-N10
S-N20, N21
S-N25
S-N35
S-N50
S-N50
S-N65
S-N80
S-N125
S-N150
S-N180
*3
with
S-N10
S-N10
2
S-N10
S-N10
S-N11, N12
S-N20
S-N20
S-N20
S-N25
S-N25
S-N50
S-N50
S-N65
S-N80
S-N95
S-N150
S-N180
S-N220
S-N300
S-N300
INV
IM
INV
IM
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents