Wiring of the control circuit of the FR-F740-01800 or more
For wiring of the control circuit of the FR-F740-01800 or more, separate away from wiring of the main circuit.
Make cuts in rubber bush of the inverter side and lead wires.
Rubber bush
(view from the inside)
Make cuts along the lines inside with
a cutter knife and such.
(6) When connecting the control circuit and the main circuit separately to the power supply
(separate power)
<Connection diagram>
MC
R/L1
S/L2
T/L3
R1/L11
S1/L21
Remove the jumper
• FR-F720-00046 to 00250-NA, FR-F740-00023 to 00126-NA
1) Loosen the upper screws.
2) Remove the lower screws.
3) Remove the jumper
4) Connect the separate
power supply cable for the
control circuit to the lower
terminals (R1/L11, S1/L21).
When the protected circuit is activated, opening of the electromagnetic
contactor (MC) on the inverter power supply side results in power loss in
the control circuit, disabling the alarm output signal retention. Terminals
Inverter
R1/L11 and S1/L21 are provided to hold an alarm signal. In this case,
connect the power supply terminals R1/L11 and S1/L21 of the control
circuit to the primary side of the MC.