N700E INSTRUCTION MANUAL
`
CAUTION FOR UL/cUL REQUIREMENTS
- THE HYUNDAI HEAVY INDUSTRY N700E INVERTER UL FILE NUMBER IS E205705.
CONFIRMATION OF UL LISTING CAN BE FOUND ON THE UL WEB SITE : www.ul.com
- DO NOT CONNECT OR DISCONNECT WIRING, OR PERFORM SIGNAL CHECKS WHILE
THE POWER SUPPLY IS TURNED ON.
- THERE ARE LIVE PARTS INSIDE THE INVERTER. NEVER TOUCH THE PRINTED WIRING
BOARD(PWB) WHILE THE POWER SUPPLY IS TURNED ON.
- [WARNING] THE BUS CAPACITOR DISCHARGE TIME IS 10 MINUTES. BEFORE STARTING WIRING
OR INSPECTION, SWITCH POWER OFF, WAIT FOR MORE THAN 10 MINUTES, AND CHECK FOR
RESIDUAL VOLTAGE BETWEEN TERMINAL P(+) AND N(-) WITH A METER ETC., TO AVOID HAZARD
OF ELECTRICAL SHOCK.
- [SHORT CIRCUIT RATING] THIS INVERTER IS SUITABLE FOR USE ON A CIRCUIT CAPABLE OF
DELIVERING NOT MORE THAN 5000ARMS SYMMETRICAL AMPERES, 480 VOLTS FOR HF TYPE
AND 240 VOLTS FOR LF TYPE MAXIMUM.
BRANCH CIRCUIT SHORT CIRCUIT PROTECTION SHALL BE PROVIDE BY FUSE ONLY
- [OVER SPEED PROTECTION] THIS INVERTER DOES NOT PROVIDE OVER SPEED PROTECTION.
- [OVER LOAD PROTECTION] THIS INVERTER PROVIDES MOTOR OVER LOAD PROTECTION.
OVER LOAD PROTECTION LEVEL IS 50~200% OF FULL LOAD CURRENT. THE PROTECTION LEVEL
IS 20~200% OF FULL LOAD CURRENT. THE PROTECTION LEVEL CAN BE ADJUSTED BY CODE B07.
REFER TO THE N700E USER GUIDE OR CATALOG.
- [MOTOR OVERTEMPERATURE] MOTOR OVERTEMPERATURE SENSING IS NOT PROVIDED BY THE
DRIVE.
- [ENVIRONMENT]
MAXIMUM
TEMPERATURE
AMBIENT HUMIDITY
STORAGE
TEMPERATURE
VIBRATION
ALTITUDE
AMBIENCE
POLLUTION DEGREE
AMBIENT
50℃
90% RH OR LESS(NO CONDENSING)
-20~60℃
5.9㎨ OR LESS
ALTITUDE 3,280 ft OR LESS
INDOORS(NO CORROSIVE AND FLAMMABLE GASES,
OIL MIST, DUST AND DIRT)
2