Hyundai N700E Instruction Manual page 60

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL
Func-
Name
code
Overload Restriction
Overload overvoltage
b06
Restriction mode selection
Overload restriction level
b07
setting
Overload restriction
b08
constant setting
Software Lock Mode
Software lock mode
b09
selection
Run-
time
Edit
Select overload or overvoltage restriction modes
0.... Overload, overvoltage restriction mode OFF
X
1.... Only overload restriction mode ON
2.... Only overvoltage restriction mode ON
3.... Overload overvoltage restriction mode ON
Sets the level for overload restriction, between 20%
and 200% of the rated current of the inverter,
X
setting range 0.2x(inverter rated current) ~
2.0x(inverter rated current)
Set the deceleration rate when inverter detects
overload, range is 0.1 to 10.0 and resolution is 0.1
Motor
current
X
Output
frequency
Prevents parameter changes, in four
options, option codes:
0.... All parameters except b09 are locked
when SFT from terminal is on
1.... All parameters except b09 and out-
X
put frequency F01 are locked when
SFT from terminal is ON
2.... All parameters except b09 are locked
3.... All parameters except b09 and output
frequency F01 setting are locked
4-19
Description
(b07)
(b08)
Defaults
3
180%
1.0sec
0

Hide quick links:

Advertisement

Table of Contents
loading