UP/DOWN Function [UP, DOWN]
• The Inverter output frequency can be changed with the UP and DOWN intelligent input terminals.
• Assign 18 (UP) and 19(DN) to two of the intelligent input terminals 1~6
•This function will not operate when the external analog frequency command or the jogging operation is used.
• Acceleration time operates according to F02, F03 when UP/DOWN terminal is ON.
O peration com m and
(FW /RV)
U P
DO W N
O utput frequency
Option
Terminal
Code
Symbol
18
UP
19
DOWN
Valid for inputs:
Required setting
Notes:
• Be sure to set the run source setting
A02=01 or 02.
Input
Function Name
State
ON
UP Function
OFF
ON
DOWN
Function
OFF
C01,C02,C03,C04,C05,C06
A02=01 or 02
Description
Accelerating motor from present frequency.
(Output frequency increases.)
Motor output acts normally.
Decelerating motor from present frequency.
(Output frequency decreases.)
Motor output acts normally.
Example:
FW/RV
SW4
CM1
6
5
5-17
Inverter doesn't accelerate
and decelerate, if U P ,
DO W N term inal is turned
O N sim ultaneously.
DOWN
UP
0/1
SW2
SW1
4
3
2
1