N700E INSTRUCTION MANUAL
Output Deviation for PID Control [OD]
The PID loop error is defined as the magnitude(absolute value)
of the difference between the Set point (target value) and the
process Variable (actual value).
When the error magnitude exceeds the press value for C24,
the [OD] terminal signal turns on.
Refer to the PID loop operation.
Option
Terminal
Code
Symbol
4
OD
Valid for inputs:
Required setting
Notes:
• The default difference value is set to 10%.
To change the value, change parameter C24.
(deviation level)
Function Name
Output deviation
for PID control
C13, C14, C15, C24
4
Input
State
When PID error is more than the set threshold
ON
for the deviation signal
When PID error is less than the set threshold
OFF
for the deviation signal
5-25
Description