Intelligent Output Terminal Function - Hyundai N700E Instruction Manual

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL
`
5.4

Intelligent Output Terminal Function

Frequency Arrival Signal [FA1]/[FA2]
Frequency Arrival [FA1] and [FA2] signals indicate when the output frequency accelerates or decelerates to
arrive at a constant frequency. Refer to the figure below.
Frequency Arrival [FA1](upper graph) turns on when the output frequency gets within 0.5Hz below or 1.5Hz
above the target constant frequency.
The timing is modified by a small 60ms delay. Note the active low nature of the signal, due to the
open collector output.
Frequency Arrival [FA2] (lower graph) uses thresholds for acceleration and deceleration to provide more
timing flexibility than [FA1].
Parameter C22 sets the arrival frequency threshold for acceleration, and parameter C23 sets the thresholds
for deceleration.
This signal also is active low and has a 60ms delay after the frequency thresholds are crossed.
Option
Terminal
Function Name
Code
Symbol
Frequency arrival
1
FA1
type 1 signal
Frequency arrival
2
FA2
type 2 signal
Valid for inputs:
C13, C14,C15, C22, C23
Required setting
(none)
Notes:
• At the time of acceleration, an arrival signal at
a frequency between the set frequency
-0.5Hz to +1.5Hz is turned on.
• At the time of deceleration, an arrival signal at
a frequency between the set frequency
+0.5Hz to -1.5Hz is turned on.
• The delay time of the output signal is 60m
(nominal).
Input
State
ON
when output to motor is at the set frequency
when output to motor is off, or in any acceleration
OFF
or deceleration ramp
when output to motor is at or above the
ON
set frequency the holds for, even if in acceleration
or deceleration ramps
when output to motor is off, or during acceleration
OFF
or deceleration before the respective thresholds
are crossed
5-22
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents