N700E INSTRUCTION MANUAL
Func-
Name
code
Automatic Voltage Regulation (AVR) Function
A52
AVR function selection
A53
Motor input voltage setting
Second Acceleration and Deceleration Functions
Second acceleration time
A54
setting
Second deceleration time
A55
setting
Two stage acce1/dece1
A56
switching method selection
Acc1 to Acc2 frequency
A57
transition point
Decel to Dec2 frequency
A58
transition point
Run-
time
Edit
Automatic (output) voltage regulation,
selects from three type of AVR functions
three option codes:
0... Constant ON
X
1... Constant OFF
2... OFF during deceleration
The AVR feature keeps the inverter
output waveform at a relatively constant
amplitude during power input fluctuations
220V class inverter settings:
X
380V class inverter settings:
Duration of 2nd segment of acceleration, range is
0.1 to 3000 sec.
Second acceleration can be set by the [2CH]
terminal input or frequency transition setting
Duration of 2nd segment of deceleration, motor
range is 0.1 to 3000 sec.
Second acceleration can be set by the
[2CH] terminal input or frequency
transition setting
Two options for switching from 1st to 2nd
accel/decel:
0.... 2CH input from terminal
1.... transition frequency
X
Output frequency at which Accel 1 switches to Acce1
X
2, range is 0.00 to 400.0Hz in units of 0.01Hz.
Output frequency at which Decel 1 switches to
X
Dece1 2, range is 0.00 to 400.0Hz in units of 0.01Hz.
4-12
Description
.... 200/220/230/240
.... 380/400/415/440/460/480
ACC2
ACC1
2CH
Time
Defaults
2
220V/
380V
30.0sec
30.0sec
0
0.00Hz
0.00Hz