Communication sequence
The communication sequence is as follows
Frame start : Frame start is recognized by signal line data transmitted.
Frame completion : Frame completion is recognized by no data during correspond 4, 5-character time.
Frame 1: Transmit from external controller to inverter.
Frame 2: Indication reflects from inverter to external controller
Communication frame type and form
External controller transmit frame
Communication
number
Communication
number
Command
Parameter
Parameter
number
CRC Hi
CRC Lo
Inverter response frame
Communication
number
Communication
number
Command
Byte Number
Data 1
Data N
CRC Hi
CRC Lo
* Frame Size = 5 + Request parameter number x 2
External
Frame 1
controller
Inverter
Command
Parameter
Description
Inverter
Communication
number
Frame type
Parameter
Request parameter
number
-
-
Byte
Order
Number
Description
Inverter
Communication
number
Frame type
Data Byte number
Parameter 1
Parameter N
-
-
Frame 2
Wait time
Parameter Count
Data size
1 byte
1~32
1 byte
0x03
1
2 byte
2
1
2 byte
2
1 byte
Higher 8bit of 16bit CRC
1 byte
Lower 8bit of 16bit CRC
• • • •
Data 1
Data N
Data size
1 byte
1~32
1 byte
0x03
1 byte
Request parameter number x 2
2 byte
Parameter value
2 byte
Nth parameter value
1 byte
Higher 8bit of 16bit CRC
1 byte
Lower 8bit of 16bit CRC
9-2
CRC Hi
CRC Lo
Specifications
st
byte : Group
nd
byte : Index (note1)
st
byte : 0x00
nd
byte : N(0x01~0x08)
CRC Hi
CRC Lo
Specifications

Hide quick links:

Advertisement

Table of Contents
loading