N700E INSTRUCTION MANUAL
`
Terminal
symbol
P24
H
O
Frequency
commanding
OI
L
Monitor
FM
terminal
11
12
collector
Intelligent
Output
terminals
AL0
AL1
AL2
CM2
Terminal name
External power
supply terminal
External power connection terminal for intelligent input terminals.
for input
When assign 13[AT signal] to code C01~C06
• AT signal OFF :
Frequency
command
power terminal
terminal O-L(0~10V)
• AT signal ON :
Frequency
commanding
terminal
(voltage
When not assign 13[AT signal] to code C01~C06 It is possible to
commanding)
commend frequency use the algebraic sum of both the voltage
and current input
Frequency
commanding
• Frequency limit by frequency order method :
terminal(current
Voltage input order(DC 0~10V)
command)
A61 : Minimum frequency(0Hz), A62:Maximum frequency(Enable
to A04 Setting value)
Frequency
Current input order(4~20mA)
command
A63 : Minimum frequency(0Hz), Maximum frequency(Enable to
common terminal
A04 Setting value)
Analog output frequency monitor/ analog output current monitor/
Frequency monitor
analog output voltage monitor
Frequency Arrival [FA1] and [FA2] signals
indicate when the output frequency accelerates
or decelerates to arrive at a constant frequency.
Refer to the figure below.
Frequency
Arrival
Signal
(FA1,FA2)
Open
When the [RUN] signal is selected as an
Run
intelligent output terminal, the inverter outputs a
Signal
signal on that
(Run)
terminal when it is in the Run Mode.
Overload
Advance
When the output current exceeds a preset value,
Notice
the [OL] terminal signal turns on
Signal(OL)
Output
When the error magnitude exceeds the press
Deviation
value for C21 the [OD] terminal signal turns on.
for PID
Refer to the PID loop operation.
Alarm
The Inverter alarm signal is active when a fault
signal
has occurred and it is in the Trip Mode.
At normal status, power off(initial setting value) : Al0 - AL1(closed)
At abnormal status : AL0 - AL2(closed)
Relay
-
Contact rating : 250V AC 2.0A(resistor 1oad) 0.2A(inductor load)
Common
Intelligent output terminal's common terminal
terminal
It is possible to command frequency using voltage signal
It is possible to command frequency using current signal
terminal OI-L (4~20mA)
30V DC 3.0A(resistor 1oad) 0.7A(inductor load)
(minimum 100V AC 10mA, 5V DC 100mA)
5-2
Description
Output
Terminal
Specification
DC 27Vmax
50mA max