(3) Common specification for 200V/400V class
Inverter model
Control system(Note5)
Output frequency range
(Note3)
Frequency accuracy (Note4)
Frequency resolving power
Voltage/frequency
characteristic
Overload current rate
Acceleration/
Deceleration
DC Braking
Operator
Frequency
Operator
Run/
Stop
Intelligent input terminal
Frequency monitor
Intelligent output
terminal (Relay)
Intelligent output
terminal
(Open collector)
Other functions
Space vector modulation PWM system
0.01∼400Hz
Digital command ±0.01% for Max. frequency, analog frequency ±0.1%
(25±10℃)
Digital setting : 0.01HZ, Analog setting : Max. frequency / 1,000
V/f control (constant torque, reduced torque), free V/f control
150%, 60sec
0.1∼3000.0 sec (Director, curve setting)
On starting and decelerating by stop command, inverter operates under
operation setting frequency. Or inverter operates with external input (Breaking
power, time, frequency can be set.)
Setting by up/down key
Extend
Input voltage : DC0∼+10V (Input impedance 50KΩ)
signal
Input current : 4∼20mA (Input impedance 200Ω)
Run / Stop key (Forward / Reverse function mode)
Extend
Forward run / stop (1a connect, 1b selection possibility)
signal
FW(Forward), RV(Reverse),
CF1~4(Multi-speed bit 1~4), RS(reset),
AT(Analog input change), USP(USP function)
EXT(external trip), FRS(free-run stop), JG(jogging),
SFT(software lock), STA(start), STP(keep), F/R(forward/reverse)
UP(remote control UP), DOWN(remote control DOWN), O/R(Local Keypad
Operation), T/R(Local Terminal Input Operation)
PIDIR(PID Integral Reset), PIDD(PID Disable)
Analog meter (DC0~10V full scale. Max ∙ 1mA)
Output frequency, output current and output voltage
Run(Run signal), FA1(Frequency arrival signal), FA2(Frequency arrival signal),
OL(Overload advance notice signal), OD(Output deviation for PID control)
Run(Run signal), FA1(Frequency arrival signal), FA2(Frequency arrival signal),
OL(Overload advance notice signal), OD(Output deviation for PID control)
AVR function, curved accel/decel. profile, upper and lower limiters,
16-stage speed profile, fine adjustment of start frequency, BRD function
carrier frequency change(0.5 to 16Khz), frequency jump, gain and bias setting,
process jogging, electronic thermal level adjustment, retry function,
trip history monitor, auto tuning, V/f characteristic selection, Speed Search
automatic torque boost, frequency conversion display, USP function
Common specification for all model