N700E INSTRUCTION MANUAL
Func-
Name
code
Other Function
Communication time out
b28
setting
Communication time out
b29
operation mode
b30
Display code setting
nd
2
Communication
b31
Channel (option) baud
rate setting
BRD(Dynamic braking) Function
b32 BRD selection
b33 BRD using ratio
Run-
time
Edit
This function detects communication time out in case of
communication cut off.
To set the detection time of time out, "code b28" is used.
0: No detect time out
1~60 : detect time out when communication cut off
[ Unit : second ]
Set communication time out operation mode
0 : Always active
1 : Active in case of inverter is running
Set Initial display status of d1 ~d13 after power on.
Set value 1 to 13 for d1 to d13.
nd
Setting 2
485 communication channel baud rate
1 : 2400bps
2 : 4800bps
3 : 9600bps
4 : 19200bps
Three options: select codes:
0 : Invalid : BRD doesn't operate
X
1 : During run : valid (BRD operates.)
During stop : invalid (BRD doesn't operate.)
2 : During run, stop, valid (BRD operates.)
Sets the BRD using ratio, range is 0.0 to 50.0% in units
of 0.1%.
When inverter exceeds the usage ratio, a trip occurs.
BRD using ratio ( % ) =
X
BRD
operation
4-22
Description
(t1 + t2 + t3)
100sec
t1
t2
ON
ON
100sec
Defaults
0
0
1
3
1
× 100
10.0%
t3
ON