4.5.4 Through a Prefabricated Chimney

The best method to make an installation
through a prefabricated chimney is to run a 3"
stainless steel liner inside the prefabricated
chimney (or a 4" stainless steel liner depending
on the Equivalent Vent Length calculated in
Section 4.3 Equivalent Vent Length (EVL)).
1. Position stove following clearances given in
Section 3.2 Minimum Clearances to
Combustibles
manufacturer's instructions.
2. Install a cleanout tee to the stove exhaust. If
necessary, use a horizontal additional
length between the exhaust and the tee. If
you wish to center the vertical part of the
vent with the stove, a 45° elbow and a tee
can be used to route the pipe from the
exhaust towards the back center of the
stove.
3. Connect the pellet vent to the stainless steel
liner according to the vent manufacturer's
instructions.
4. Seal and install vertical roof vent. If
required, seal and install a storm collar.
WARNING: IN THE U.S., THE USE OF A STAINLESS STEEL LINER IS MANDATORY. IN
CANADA, IT IS NOT MANDATORY BUT IS STRONGLY RECOMMENDED.
NOTE: VENTING DIRECTLY IN AN OVERSIZED CHIMNEY AND OMIT THE USE OF A
STAINLESS STEEL LINER CAN AFFECT CHIMNEY DRAFT AND DECREASE STOVE
PERFORMANCES.