 The flue is not properly installed. Make sure the venting system meets the criteria in the
installation section of this manual as well as the venting system manufacturer's instructions.
 The flue is blocked or needs cleaning. One of the following components is obstructed or
blocked; air intake shutter, combustion blower, burn pot, heat exchangers and channels,
exhaust blower and or venting system. Refer to the maintenance section.
 The stove needs maintenance. Refer to maintenance section.
 The burn pot is not installed properly. Make sure the burn pot is well installed and locked in
place.
 The baffle is not installed properly. Make sure all three panels are well installed.
 The convection blower is defective. Go to the troubleshooting page (see Section 9.2
Testing Components) on the LCD screen and test the convection blower.
 The convection blower needs maintenance. Carefully clean blower housing and make sure
blower louvers are not blocked.
NOTE: IF THE CODE APPEARS MORE THAN THREE TIMES, THE LCD SCREEN WILL LOCK
ITSELF UP AND YOU WILL NEED TO CALL A SERVICE TECHNICIAN TO UNLOCK IT.
HOPPER LID OPEN
THE HOPPER LID HAS
REMAINED OPEN FOR MORE
RESET
The hopper lid remained open for more than 3 minutes. As a security measure, the auger
stops turning and feeding pellets as soon as the hopper lid opens. It will resume normal
operation as soon as the hopper lid is closed. If the hopper lid stays open for more than 3
minutes, the stove will stop.
 The hopper lid switch is defective or misconnected. Make sure the switch is properly
connected. If it is, the hopper switch may be defective. Go to the troubleshooting page (see
Section 9.2 Testing Components) and check the functionality of the switch. Replace if
necessary.
52
THAN 3 MINUTES
DETAILS
POWER LOSS
POWER WAS INTERRUPTED
WHILE BURNING
THE FOLLOWING MAY HAVE CAUSED YOUR
PROBLEM (HOPPER LID):
• THE HOPPER LID REMAINED OPEN FOR
MORE THAN 3 MINUTES
• THE HOPPER LID SWITCH IS DEFECTIVE
OR MISCONNECTED
CONSULT OWNER'S MANUAL FOR
MORE DETAILS
BACK
RESET
Eurostar Installation and Operation Manual