Permitted Termination Location - Enerzone EUROSTAR Installation And Operation Manual

Table of Contents

Advertisement

Refer to NFPA 211 (USA) or CSA B365 (Canada) for rules for the distance of exit terminal from
windows and openings. The exit terminal of a mechanical draft system, other than a direct vent
appliance shall be located in accordance with the following.

4.4.1 Permitted Termination Location

Canada:
Min.
Letter
clearances
A
12'' (30 cm)
B
39'' (100 cm)
F
39'' (100 cm)
H
39'' (100 cm)
I
72'' (183 cm)
J
39'' (100 cm)
K
72'' (183 cm)
L
84'' (213 cm)
39'' (100 cm)
16
Clearances above grade level or any adjacent surface that might
support snow, ice, or debris
Clearance to window or door that may be opened
Clearance to corner or adjacent wall
Not to be installed above a meter/regulator assembly within 39" (100
cm) horizontally from the vertical center-line of the regulator and for 15'
vertically
Clearance to gas service regulator vent outlet or within 39'' (100 cm) of
an oil tank vent or an oil tank fill inlet
Clearance to the combustion air inlet to any other appliance
Clearance to a mechanical air supply inlet
Clearance above paved side-walk or a paved driveway located on
public property
Clearance to property boundary
A vent shall not terminate underneath a veranda, porch, or deck
Description
Eurostar Installation and Operation Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eurostar ep00055

Table of Contents