7.2
Blockage and fault memory
Fig.10
Reading out the error memory
5x
t/m
2x
7698035 - v.01 - 19022018
The boiler control unit has an error memory. This stores the 16 most re
cent blockages and the 16 most recent faults.
7.2.1
Reading out the error memory
1. Navigate to the error menu.
The
2. Press the
shutdowns)
3. Use the
(
).
4. Press the
pears on the display.
5. The error list or blocking list can be displayed by pressing the
key.
6. Press the
For example from
7. Press the
{125} {126}{127}{128} = Supplied heat output (%).
8. Press the
or
last error that occurred.
9. Press the
10. Press the
AD-4000047-01
symbol flashes in the menu bar.
key to open the menu.
appears in the display (
or
key to select the list of shutdowns (
key to confirm the selection.
{41}{42} or {43}{44}{45}{46}{47}{48}{49}{50}{51}{52} ap
key to view details of the blocking.
or
keys to view the following data:
= Number of times that the error occurred.
= Number of burning hours.
= Status.
= Sub-status.
= Flow temperature (°C).
= Return temperature (°C).
= Boiler temperature (°C).
= Outside temperature (°C).
= Heat exchanger temperature (°C).
= Internal setpoint (°C).
= Ionisation current (μA).
= Fan speed (rpm).
= Water pressure (bar).
key to interrupt the display cycle.
{137} {138}{139}{140}
or
key to view the following errors, if applicable.
key twice to go back to the main display.
7 Troubleshooting
is the number of displayed
) or errors
appears with a flashing
or
=
15