Operation; Use Of The Control Panel; Shutdown; Frost Protection - REMEHA Gas 210 ECO PRO Series Installation, User And Service Manual

High-efficiency floor-standing gas boiler
Hide thumbs Also See for Gas 210 ECO PRO Series:
Table of Contents

Advertisement

8 Operation

8
Operation
8.1

Use of the control panel

8.2

Shutdown

8.3

Frost protection

46
The display on the control panel provides information about the operating
status of the boiler and any errors.
The manual for the control panel provides information on altering and
reading out parameters, the meaning of fault codes and the deletion of the
fault memory.
See
Manual for the control panel
If the central heating is not due to be used for a long period of time, it is
recommended that the boiler be disconnected from the power supply.
1. Turn the on/off switch to the off position.
2. Switch off the boiler's electrical connection.
3. Shut off the gas supply.
4. Keep the area frost-free.
Caution
In the event of low temperatures, we recommend that the installa­
tion continues to operate at a lower temperature. This will prevent
freezing.
Caution
Drain the boiler and central heating system if you are not going to
use your home or the building for a long time and there is a
chance of frost.
Set the temperature control low, for example to 10 °C.
If there is no heat demand, the boiler will only switch on to protect itself
against frost.
If the temperature of the central heating water in the boiler drops too low,
the built-in boiler protection system is activated. This system works as fol­
lows:
If the water temperature is lower than 7 °C, the heating pump switches
on.
If the water temperature is lower than 4 °C, the boiler switches on.
If the water temperature is higher than 10℃, the boiler shuts down and
the circulation pump continues to run for a short time.
To prevent the system and radiators freezing in frost-sensitive areas (e.g.
a garage), a frost thermostat or outside sensor can be connected to the
boiler.
Caution
The frost protection does not work if the boiler is out of opera­
tion.
The boiler protection only protects the boiler, not the system.
114494 - v.05 - 06022018