7. Instructions
FUN 080
Expression
Input -[ A RTR n ® B ]- Output
Function
When the input is ON, the data of register A is rotated n bits to the right (LSB direction), and stored in
B . After the operation, if the right most bit (LSB) is ON, the output is turned ON.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
A Source
n Shift bits
B Destination
Example
When X007 is changed from OFF to ON, the data of RW18 is rotated 5 bits to the right and the
result is stored in RW20.
The figure below shows an operation example.
(MSB)
F
RW18
0 1 0 0 0 0 1 0 1 0 0 1 1 0 1 0
RW20
1 1 0 1 0 0 1 0 0 0 0 1 0 1 0 0
(Result)
192
T1/T1S User's Manual