Power Supply Wiring - Toshiba PROSEC T1 User Manual

Programmable controller
Hide thumbs Also See for PROSEC T1:
Table of Contents

Advertisement

4. Installation and Wiring

4.5 Power supply wiring

!
CAUTION
Wire the power source to the T1/T1S power supply terminals.
Power source
· Power conditions:
Rated voltage
Frequency
Power consumption
Retentive power
interruption
· 1.25 mm
· The power cable should be separated from other cables.
78
T1/T1S User's Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
1. Turn off power before wiring to minimize the risk of electrical shock.
2. Applying excess power voltage to the T1/T1S can cause explosion or fire.
Apply power of the specified ratings described below.
Line filter
AC power supply type
100 to 240 Vac, +10/-15 %
50/60 Hz, ±5 %
30 VA or less (T1-16/T1-28)
38 VA or less (T1-40)
45 VA or less (T1-40S)
Continuous operation for less than 10 ms
2
(16 AWG) twisted-pair cable should be used for the power cable.
Insulation
transformer
DC power supply type
24 Vdc, +20/-15 %
12 W or less (T1-16/T1-28)
18 W or less (T1-40)
18 W or less (T1-40S)
6F3B0250
T1
-