7. Instructions
FUN 061
Expression
Input -[ A DFL B ® C ]- Output
Function
When the input is ON, this instruction calculates the following formula to perform digital filtering for
input data A by filter constant by B , and stores the result in C .
(
)
=
-
´
+
y
1
FL
x
FL y
n
n
is input data specified by A
Here; x
n
FL is filter constant, 1/10000 of data specified by B (data range: 0 to 9999)
y
is output data to be stored in C
n
y
is output data at last scan
n-1
This instruction is useful for filtering the analog input signal. C+1 is used for internal work data.
Execution condition
Input
OFF
No execution
ON
Execution (FL is limited within the range of 0 to 9999)
Operand
Name
A Input data
B Filter constant
C Output data
Example
The filtered data of XW04 is stored in D0110. (D0111 is used for internal work data)
When D0100 value is small
XW04
178
T1/T1S User's Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
DFL
Digital Filter
´
-
n
1
Operation
Device
X
Y
R
S
T.
C. XW YW RW SW T
D0110
Time
Output
OFF
ON
Register
C
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
When D0100 value is large
XW04
T1S only
Constant Index
D
I
J
K
Ö
Ö
Ö
Ö
Ö
Ö
Ö
D0110
Time
6F3B0250