Toshiba PROSEC T1 User Manual page 237

Programmable controller
Hide thumbs Also See for PROSEC T1:
Table of Contents

Advertisement

FUN 154
CLND
Expression
Input -[ A CLND ]- Output
Function
When the input is ON, the built-in clock/calendar is set to the date and time specified by 6 registers
starting with A . If an invalid data is contained in the registers, the operation is not executed and the
output is turned ON.
Execution condition
Input
OFF
No operation
ON
Execution (data is valid))
No execution (data is not valid)
Operand
Name
A Start of table
Example
When R020 is ON, the clock/calendar is set according to the data of D0050 to D0055, and the
output is OFF (R0031 is OFF).
If D0050 to D0055 contains invalid data, the setting operation is not executed and the output is
turned ON (R0031 comes ON).
F
D0050
H00
D0051
H00
D0052
H00
D0053
H00
D0054
H00
D0055
H00
Note
· The day of the week is automatically.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Set calendar
Operation
Device
X
Y
R
S
T.
C. XW YW RW SW T
Allowable data range (2-digit BCD)
8 7
0
Year
H00 to H99 (1990 - 2089)
Month
H01 to H12
Day
H01 to H31
Hour
H00 to H23
Minute
H00 to H59
Second
H00 to H59
Output
OFF
OFF
ON
Register
C
Ö
Ö
Ö
Ö
Ö
Ö
Basic Hardware and Function
6F3B0250
7. Instructions
T1S only
Constant Index
D
I
J
K
Ö
Calendar
LSI
235