Toshiba PROSEC T1 User Manual page 153

Programmable controller
Hide thumbs Also See for PROSEC T1:
Table of Contents

Advertisement

MCS
Master control set / reset
MCR
Expression
Input
[ MCS ]
[ MCR ]
Function
When the MCS input is ON, ordinary operation is performed. When the MCS input is OFF, the state of
left power rail between MCS and MCR is turned OFF.
Execution condition
MCS
input
OFF
Sets OFF the left power rail until MCR
ON
Ordinary operation
Operand
No operand is required.
Example
When X000 is OFF, Y021 and Y022 are turned OFF regardless of the states of X001 and X002.
Equivalent circuit
X000
X001
X002
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Operation
Y021
Y022
Output
-
-
Note
· MCS and MCR must be used as a pair.
· Nesting is not allowed.
Basic Hardware and Function
6F3B0250
7. Instructions
151