Toshiba PROSEC T1 User Manual page 193

Programmable controller
Hide thumbs Also See for PROSEC T1:
Table of Contents

Advertisement

FUN 079
Expression
Input -[ RTL1 A ]- Output
Function
When the input is ON, the data of register A is rotated 1 bit to the left (MSB direction). The pushed out
bit state is stored in the right most bit (LSB) and in the carry flag (CF = S050). After the operation, if the
left most bit (MSB) is ON, the output is turned ON.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
A Operation data
Example
When X008 is changed from OFF to ON, the data of RW15 is rotated 1 bit to the left.
The figure below shows an operation example.
(MSB)
F
E
1 1 1 0 0 1 1 1 0 0 1 1 1 0 1 0
CF
1
1 1 0 0 1 1 1 0 0 1 1 1 0 1 0 1
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
RTL1
1 bit rotate left
Operation
When MSB = 1
When MSB = 0
Device
X
Y
R
S
T.
C. XW YW RW SW T
D C
B
A
9
8
7
R002 is turned ON
Output
OFF
ON
OFF
Register
Ö
Ö
Ö
Ö
(LSB)
6
5
4
3
2
1
0
RW15
RW15 (Result)
Basic Hardware and Function
7. Instructions
CF
-
Set or reset
Set or reset
Constant Index
C
D
I
J
K
Ö
Ö
Ö
Ö
Ö
6F3B0250
Ö
191