7. Instructions
FUN 026
TNOT
Expression
Input -[ A TNOT ( n ) B ]- Output
Function
When the input is ON, the data of n registers starting with A are bit-inverted and transferred to n
registers starting with B in a block. The allowable range of the table size n is 1 to 1024 words.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
A Start of source
n Table size
B Start of
destination
Example
When R010 is ON, the data of D0600 to D0604 (5 registers) are bit-inverted and transferred to
D0865 to D0869, and the output is turned ON.
D0600
H00FF
D0601
H0000
D0602
H1234
D0603
H5555
D0604
H89AB
Note
· The source and destination tables can be overlapped.
160
T1/T1S User's Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Table invert transfer
Operation
Device
X
Y
R
S
T.
C. XW YW RW SW T
Bit-invert
and transfer
Output
OFF
ON
Register
C
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
D0865
HFF00
D0866
HFFFF
D0867
HEDCB
D0868
HAAAA
D0869
H7654
6F3B0250
T1S only
Constant Index
D
I
J
K
Ö
1 - 1024
Ö
5 registers