Toshiba PROSEC T1 User Manual page 145

Programmable controller
Hide thumbs Also See for PROSEC T1:
Table of Contents

Advertisement

Positive pulse contact
P
Expression
A
Input
Output
P
Function
When the input is ON and the device A is changed from OFF to ON (OFF at last scan and ON at this
scan), the output is turned ON.
This instruction is used to detect the device changing from OFF to ON.
Execution condition
Input
OFF
Regardless of the state of device A
ON
State of device A is OFF
State of device A is ON
Operand
Name
A Device
Example
R100 comes ON for only 1 scan when X000 is ON and X003 changes to ON.
X000
X003
R100
1 scan time
Note
· The maximum usable number in a program is 2048.
(