7. Instructions
FUN 106
Expression
Input -[ A+1 × A D< B+1 × B ]- Output
Function
When the input is ON, the double-word data of A+1 × A and B+1 × B are compared, and if A+1 × A is less
than B+1 × B , the output is turned ON.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
A Compared
data
B Reference data
Example
When R010 is ON, the data of D0101×D0100 is compared with the constant data 427780, and if
the data of D0101×D0100 is less than 427780, R014 is turned ON.
If the data of D0101×D0100 is 250000, R014 is turned ON.
D0101×D0100
If the data of D0101×D0100 is 430000, R014 is turned OFF.
D0101×D0100
Note
· This instruction deals with the data as double-word integer (-2147483648 to 2147483647).
206
T1/T1S User's Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Double-word less than
D<
Operation
A+1 × A < B+1 × B
A+1 × A ³ B+1 × B
Device
X
Y
R
S
T.
C. XW YW RW SW T
<
250000
³
430000
Output
OFF
ON
OFF
Register
C
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Constant
427780
Constant
427780
6F3B0250
Constant Index
D
I
J
K
Ö
Ö
Ö
Ö
R014 is ON