8. Special I/O Functions
8.1 Special I/O function overview
The T1/T1S supports the special I/O functions as listed below.
Function name
Variable input filter
constant
High
speed
counter
Interrupt input function Immediately activates the corresponding I/O interrupt
Analog setting function The value of the analog setting adjuster is converted
Pulse output function
PWM output function
NOTE
268
T1/T1S User's Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Input filter constant (ON/OFF delay time) can be set by
user program. The setting range is 0 to 15 ms
(1 ms units). Default value is 10 ms. This function is
applied for X000 to X007 (8 points as a block).
Single phase
Counts the number of pulses of single phase pulse
up-counter
train. 2 channels of pulse input are available. The
countable pulse rate is up to 5 kHz for each channel.
Channel 1 ¼ X000 count input, X002 reset input
Channel 2 ¼ X001 count input, X003 reset input
Single phase
Counts the number of pulses in a specified sampling
speed-
time. The sampling time setting is 10 to 1000 ms (10
counter
ms units). 2 channels of pulse input are available. The
countable pulse rate is up to 5 kHz for each channel.
Channel 1 ¼ X000 count input
Channel 2 ¼ X001 count input
Quadrature
Counts the 2-phase pulses whose phases are shifted
bi-pulse
90° each other. Counts up when phase A precedes,
counter
and counts down when phase B precedes. The
countable pulse rate is up to 5 kHz.
Phase A ¼ X000
Phase B ¼ X001
Reset ¼¼ X002
program when the interrupt input is changed from OFF
to ON (or ON to OFF). 2 points of interrupt input are
available.
X002 ¼ Interrupt 1 (I/O interrupt program #3)
X003 ¼ Interrupt 2 (I/O interrupt program #4)
into digital value (0 to 1000) and stored in the SW
register. 2 adjusters are provided on the T1/T1S.
V0 ¼ SW30
V1 ¼ SW31
Variable frequency pulse train can be output. The
available pulse rate is 50 to 5000 Hz (1 Hz units).
Y020 ¼ CW or Pulse (PLS)
Y021 ¼ CCW or Direction (DIR)
Variable duty cycle pulse train can be output. The
available ON duty setting is 0 to 100 % (1 % units).
Y020 ¼ PWM output
The above special I/O functions, except the v
analog setting functions, are available only in the DC input types.
Function summary
ariable input filter constant
Remarks
SW16 setting
is necessary to
use this
function. (Note)
Only one
among these 4
functions can
be selected.
SW16 is used
to select the
function.
(Note)
No function
selection is
required.
Either one
between these
2 functions can
be used.
SW26 is used
to select the
function. (Note)
and