3.2 Application precautions for output signals
!
WARNING
!
CAUTION
(1) 2 points of solid-state output
The leading 2 points of output (Y020 and Y021) are solid-state outputs, transistors on the
DC input types and triacs on the AC input types.
These solid-state outputs are suited for frequent switching applications.
Note that the specifications of the solid-state outputs and other outputs (relays) are
different.
(2) Switching life of output relays
Expected relay life is more than 100,000 electrical cycles at rated maximum voltage and
current, and more than 20 million mechanical cycles. The expected contact life (electrical
cycles) is shown on the table below.
AC
load COSf = 1
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Configure emergency stop and safety interlocking circuits outside the T1/T1S.
Otherwise, malfunction of the T1/T1S can cause injury or serious accidents
1. Turn on power to the T1/T1S before turning on power to the loads. Failure
to do so may cause unexpected behavior of the loads.
2. Configure the external circuit so that the external 24 Vdc power required
for the transistor output circuits and power to the loads are switched on/off
simultaneously. Also, turn off power to the loads before turning off power to
the T1/T1S.
3. Install fuses appropriate to the load current in the external circuits for the
outputs. Failure to do so can cause fire in case of load over-current.
Load voltage
Load
Expected life
current
(thousand)
110 Vac,
2 A
1 A
0.5 A
110 Vac,
2 A
1 A
COSf = 0.7
0.5 A
220 Vac,
2 A
1 A
COSf = 1
0.5 A
220 Vac,
2 A
1 A
COSf = 0.7
0.5 A
3. I/O Application Precautions
Load voltage
340
DC
24 Vdc,
720
load L/R = 0 ms
1,600
150
24 Vdc,
320
L/R = 15 ms
700
220
48 Vdc,
500
L/R = 0 ms
1,100
48 Vdc,
100
L/R = 15 ms
210
110 Vdc,
460
L/R = 0 ms
110 Vdc,
L/R = 15 ms
Basic Hardware and Function
6F3B0250
Load
Expected life
current
(thousand)
2 A
280
1 A
600
0.5 A
1,300
2 A
60
1 A
150
0.5 A
350
1 A
200
0.5 A
420
0.5 A
130
0.2A
420
0.5 A
200
0.2 A
550
0.2 A
150
0.1 A
350
65