Toshiba PROSEC T1 User Manual page 305

Programmable controller
Hide thumbs Also See for PROSEC T1:
Table of Contents

Advertisement

Error message and related information
Event
Operand error
Pair inst error
Peripheral LSI err
Program BCC error
RAM check error
Scan time over
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Info 1
Info 2
Info 3
Program
Address
type -
in the
block No.
block
Program
Address
type -
in the
block No.
block
Error
code
Illegal
BCC
Error
Error data Test data
address
Scan time
10. Troubleshooting
Special
Meaning and countermeasures
device
A register/device which is not supported by
the T1/T1S is programmed. (Error down)
Correct the program.
The timer or counter register is duplicated in
the program. (Error down)
Correct the program.
The subroutine number programmed with
CALL or SUBR instruction is out of the range.
(Error down)
T1 ...... 0 to 15
T1S .... 0 to 255
Correct the program.
Index modification is programmed for
instructions in which the index modification is
not allowed. (Error down)
Correct the program.
The combination is illegal for MCS-MCR,
JCS-JCR or FOR-NEXT instructions. (Error
down)
Correct the program.
A MCS-MCR is programmed inside other
MCS-MCR segment. (Error down )
Correct the program.
A JCS-JCR is programmed inside other
JCS-JCR segment. (Error down )
Correct the program.
S004
CPU hardware error has been detected in the
S016
power-up initialization. (Error down and
programming tool cannot be connected)
Replace the unit if the error remains after
power OFF and ON again.
S006
BCC error has been detected in the user
S030
program in the RAM. (Error down)
If the error remains after power OFF and ON
again, reload the program and execute
EEPROM write operation.
S004
In the power-up initialization, an error has
S012
detected by RAM read/write checking. (Error
down)
Replace the unit if the error remains after
power OFF and ON again.
S006
The scan time has exceeded 200 ms. (Error
S031
down)
Correct the program to reduce the scan time
or use WDT instruction to extend the check
time.
Basic Hardware and Function